Customization: | Available |
---|---|
After-sales Service: | 24-7 |
Warranty: | 12 Months or 1500 Operation Hours |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Diesel Generator Set Data | |||
Set Type: | KMS-400 | ||
Standby Power: | 440KW/550KVA | ||
Prime Power: | 400KW/500KVA | ||
Rated Current: | 720(A) | ||
Rated Frequency: | 50(Hz) | ||
Start-up time: | 5~6(s) | ||
Power Factor: | 0.8(Lag) | ||
Rated Voltage: | 400/230(V) | ||
Diesel Engine Data | |||
Manufacturer: | CCEC | ||
Model: | KTA19-G4 | ||
Prime/Standby Power: | 448KW/504KW | ||
Rated Speed: | 1500(r/min) | ||
Cycle: | 4 stroke | ||
Cylinder Arrangement: | 6 in line | ||
Displacement: | 18.9L | ||
Bore and Stroke: | 159*159(mm) | ||
Compression Ratio: | 14.5:1 | ||
Governor Type: | Electronic | ||
Start battery voltage: | 24V DC | ||
Air Intake System | |||
Air Intake System: | Turbo, Water/Air Cooling | ||
Max Intake Restriction: | 6.23kPa | ||
Burning Capacity: | 579L/s | ||
Air Flow: | 9800L/s | ||
Exhaust System | |||
Exhaust Gas Flow: | 1604L/s | ||
Exhaust Temperature: | 557ºC | ||
Max Back Pressure: | 10kPa | ||
Fuel System | |||
Fuel System: | PT type fuel pump, EFC | ||
100%( Prime Power) Load: | 203g/kwh | ||
50%( Prime Power) Load: | 216g/kwh | ||
Oil System | |||
Total Oil Capacity: | 50L | ||
Oil Consumption: | ≤0.4g/kw·h | ||
Engine Oil Tank Capacity: | 38L | ||
Oil Pressure at Rated RPM: | 345-483kPa | ||
Cooling System | |||
Cooling Way: | Water-cooled | ||
Total Coolant Capacity: | 106L | ||
Thermostat: | 82-93ºC | ||
Max Water Temperature: | 104ºC | ||
Alternator Data | |||
Manufacturer: | SIEMENS/ MARATHON/ |
||
Excitation Mode: | Brushless and self- exciting | ||
Number of phase and Access Act: | 3-phase 4-wire | ||
Connecting Type: | "Y" type connecting | ||
Alternator Capacity: | 550KVA | ||
Alternator Efficiencies: | 95% | ||
Overload: | (PRP)110% load can run 1h | ||
Protection Level: | IP22-IP23 | ||
Insulation Class, Temperature Rise: | H/H | ||
Telephone Influence Factor (TIF): | <50 | ||
THF: | <2% | ||
Voltage Regulation, Steady State: | ≤±1% | ||
Air Cooling Flow: | 1.035m3/s | ||
Altitude: | ≤1000m |
Genset Electrical Performance | |
Voltage Regulation: | ≥±5% |
Voltage Regulation, Stead State: | ≤±1% |
Sudden Voltage Warp (100% Sudden Reduce): | ≤+25% |
Sudden Voltage Warp (Sudden Increase): | ≤-20% |
Voltage Stable Time (100% Sudden Reduce): | ≤6S |
Voltage Stable Time (Sudden Increase): | ≤6S |
Frequency Regulation, Stead State: | ≤5% |
Frequency Waving: | ≤1.5% |
Sudden Frequency Warp (100% SuddenReduce): | ≤+12% |
Sudden Frequency Warp (Sudden Increase): | ≤-10% |
FrequencyRecoveryTime(100%SuddenReduce): | ≤5S |
FrequencyRecoveryTime(Sudden Increase): | ≤5S |